Peningkatan Jalur Distribusi Tanam 20Kv Pada Kawasan Industri MM2100

Al Ayubi, Achmad Farhan (2026) Peningkatan Jalur Distribusi Tanam 20Kv Pada Kawasan Industri MM2100. Tugas Akhir (S1) - thesis, Universitas Bakrie.

[thumbnail of Cover] Text (Cover)
00. Cover.pdf.pdf - Accepted Version

Download (389kB)
[thumbnail of BAB I - III] Text (BAB I - III)
01. BAB I-III.pdf.pdf - Accepted Version
Restricted to Registered users only

Download (2MB) | Request a copy
[thumbnail of BAB IV] Text (BAB IV)
02. BAB IV.pdf.pdf - Accepted Version
Restricted to Registered users only

Download (12MB) | Request a copy
[thumbnail of BAB V] Text (BAB V)
03. BAB V.pdf.pdf - Accepted Version
Restricted to Registered users only

Download (21kB) | Request a copy
[thumbnail of Daftar Pustaka] Text (Daftar Pustaka)
04. BAB Daftar Pustaka.pdf.pdf - Accepted Version

Download (70kB)
[thumbnail of Lampiran] Text (Lampiran)
05. Lampiran.pdf.pdf - Accepted Version
Restricted to Registered users only

Download (1MB) | Request a copy

Abstract

Upgrading the 20 kV power distribution in the MM2100 Industrial Town requires placing additional cable circuits on four existing cable bridges (CIK 2, CIK 3, CIK 4, and CIK 5). This introduces additional dead, tension, and lateral loads onto environment-degraded structures. This study aims to evaluate existing concrete and steel material properties, assess structural capacity using 3D ETABS modeling, and formulate repair recommendations. Evaluation was conducted via visual inspection and Non-Destructive Testing (NDT) comprising Ultrasonic Pulse Velocity Test (UPVT), Hammer Test, Liquid Penetrant Test (PT), Coating Thickness Measurement, and Ultrasonic Thickness Meter (UTM). NDT results confirm that concrete strength meets SNI 2847:2019 minimum standards (fc = 25.50 - 39.93MPa), though minor weld defects, paint degradation, and section loss due to localized corrosion were identified. Structural analysis using ETABS per SNI 1726:2019and AISC 360-16 concludes that the existing bridges maintain adequate capacity and safety margins to support the additional 20 kV cables. Recommended actions include vegetation clearing, anti-corrosion re-coating (ISO 12944), concrete spalling repairs, and gusset plate reinforcement at critical structural joints. Keywords: Cable Bridge, 20 kV Distribution, Non-Destructive Testing (NDT), ETABS, Structural Evaluation, MM2100 Industrial Town.

Item Type: Thesis (Tugas Akhir (S1) - )
Uncontrolled Keywords: Cable Bridge, 20 kV Distribution, Non-Destructive Testing (NDT), ETABS, Structural Evaluation, MM2100 Industrial Town.
Subjects: Civil Engineering > Structural analysis (Engineering) (Analisis struktur)
Civil Engineering
Thesis > Thesis (S1)
Divisions: Fakultas Teknik dan Ilmu Komputer > Program Studi Teknik Sipil